Maintenance-free intelligent transformer breather

The maintenance-free transformer breather is an air dehumidification and purification device used for oil-immersed transformers, instrument transformers, on-load tap changers, or other electrical equipment filled with insulating liquid. The maintenance-free transformer breather is installed at the air inlet of the instrument transformer's oil storage tank. When the transformer or instrument transformer operates, the oil volume changes due to temperature variations, causing the gas inside the oil storage tank to breathe through the desiccant. Air passes through the filter at the bottom of the desiccant and the glass jar filled with silica gel into the transformer, ensuring that the inhaled air is dry (moisture is adsorbed by the desiccant) and clean (dust and impurities are blocked by the filter), thereby maintaining the cleanliness and insulation strength of the transformer oil.

Keyword:

Power IoT sensors Smart power distribution Internet of Things Smart cable tunnel gallery Smart power generation Internet of Things Smart Internet of Things

Free consultation telephone:

Product Details

Maintenance-Free Transformer Breather

 

Product Overview

 

The maintenance-free transformer breather is an air dehumidification and purification device used for oil-immersed transformers, instrument transformers, on-load tap changers, or other electrical equipment filled with insulating liquid. The breather is installed at the air inlet of the instrument transformer's oil conservator. When the transformer or instrument transformer operates, changes in oil temperature cause the oil volume to expand or contract, forcing the gas inside the oil conservator to breathe through the desiccant. Air passes through the lower filter of the desiccant and the silica gel-filled glass container into the transformer, ensuring that the inhaled air is dry (moisture is adsorbed by the desiccant) and clean (dust and impurities are blocked by the filter), thereby maintaining the cleanliness and insulation strength of the transformer oil.

 

Product Features

 

(1) Oil Cup Design: Compatible with traditional breather habits, clearly indicating the current breathing status of the transformer.

(2) Auxiliary Heating: When the ambient temperature is low, auxiliary heating is activated to prevent condensation or freezing of the bottom filter device; it also prevents the oil in the oil cup from freezing at low temperatures.

(3) Condensate Discharge: During regeneration heating, ensures rapid discharge of condensate on the glass wall.

(4) Desiccant Pulverization Treatment: The device is subjected to long-term vibration and desiccant regeneration heating, which causes desiccant pulverization. This device optimizes the structure to ensure that pulverized desiccant does not block the air inlet.

(5) Heating Device Fault Detection: Monitors heating power to determine the reliability of the heating device.

(6) Breathing Volume Monitoring: Measures the breathing volume over a cycle to detect leaks in the connecting pipe; establishes the relationship between transformer oil temperature, breathing volume, and breathing speed.


 

Product Advantages

 


   


 

Product Functions

 

1. Installed at the air inlet of the oil conservator, it prevents moist air from directly entering the transformer through drying and absorption, maintaining the excellent electrical performance of the transformer insulating oil.

2. The dryer can be heated and regenerated. Water vapor passes through the metal mesh and condenses on the glass cylinder, with water droplets flowing out of the desiccant along the glass cylinder. Desiccant regeneration heating can be achieved in two ways: according to a preset time interval or when humidity reaches 40%.

3. In case of failure, on-site and remote audible and visual alarms can be triggered, and remote monitoring of the breather status can be realized via RS485.

 

Technical Parameters

Power Environment
Control System Power Supply AC220V±10%, 50/60Hz
Electromagnetic Compatibility Test and Measurement Technology GB/T 17626.2-2006 Electrostatic Discharge Immunity Test
GB/T 17626.3-2006 Radiated Radio-Frequency Electromagnetic Field Immunity Test
GB/T 17626.4-2008 Electrical Fast Transient/Burst Immunity Test
GB/T 17626.5-2008 Surge (Shock) Immunity Test
GB/T 17626.8-2006 Power Frequency Magnetic Field Immunity Test
Environmental Tests for Electrical and Electronic Products GB/T 2423.1-2008 Test A: Low Temperature
GB/T 2423.2-2008 Test B: High Temperature
GB/T 2423.3-2006 Test Cab: Constant Damp Heat Test
Functions
Moisture Absorbent Material Colorless Silica Gel
Silica Gel Weight 1.5kg, 3kg, 5kg (Dual Tank)
Regeneration Frequency Can be set according to installation requirements; default is 30 days.
Regeneration Cycle 2 hours
Relative Humidity Threshold User Configurable; default is 60%
Dehydration Method Online Automatic Dehydration
Heating Temperature Internal heating up to 100°C, bottom heating up to 20°C
Heater Power 1.5kg: 270W, 3kg: 270W, 5kg: 360W
Output Interface RS485
Communication Protocol MODBUS RTU
Status Display 4 LEDs (Green: Running, Yellow: Left/Right Tank Heating, Red: Fault)
4 LEDs + 2 sets of 3-digit digital tubes displaying: measured temperature, measured humidity, accumulated days, and accumulated hours.
Operating Conditions
Ambient Temperature -40°C to 80°C
Relative Humidity >90%
Control Box Protection Level IP55

 

Software Copyright and Patents

 

Test Reports

 

Production, Testing, Shipping

 

Application Scenarios

Related Products

Maintenance-free intelligent transformer breather


The maintenance-free transformer breather is an air dehumidification and purification device used for oil-immersed transformers, instrument transformers, on-load tap changers, or other electrical equipment filled with insulating liquid. The maintenance-free transformer breather is installed at the air inlet of the instrument transformer's oil storage tank. When the transformer or instrument transformer operates, the oil volume changes due to temperature variations, causing the gas inside the oil storage tank to breathe through the desiccant. Air passes through the filter at the bottom of the desiccant and the glass jar filled with silica gel into the transformer, ensuring that the inhaled air is dry (moisture is adsorbed by the desiccant) and clean (dust and impurities are blocked by the filter), thereby maintaining the cleanliness and insulation strength of the transformer oil.

JC-OM700-EE Wireless Expansion Joint Sensor


The JC-OM700-EE wireless expansion joint sensor achieves online monitoring of expansion joint compensation by modifying the existing mechanical vernier caliper of GIS/GIL expansion joints or adding a digital expansion joint displacement sensor. The wireless expansion joint sensor uses a high-speed ARM chip as the main controller and a high-precision displacement sensor to sample and calculate the displacement data of the measured object in real time. It can upload data to the host computer via wireless LoRa and wired RS485.

Current monitoring sensor of arrester in switchgear


Full current measurement range: 0.050 ~ 5.000mA Full current measurement error: ± (standard reading ×1%+5μA) Record the cumulative discharge times :0 ~ 99 times Power supply: DC24V Communication interface: RS-485

Ground resistance sensor


Power supply: dc6 ~ 12V Range: 0.01 Ω- two hundred Ω  Accuracy: ± 2%rdg ± 3dgt(20℃ ± 5 ℃, below 70% RH) Communication mode: RS485 Protection grade: IP54

High frequency current sensor


Sensitivity: 5pc Detection frequency band: 50KHz ~ 100MHz Signal output: RS485 Installation position: cable connector ground wire Installation mode: clamp type, clamping

Tilt sensor


Range: ± thirty °  Voltage: 9-35v Output mode: RS485 IP67 protection level

Infrared thermal imaging camera of switch cabinet


Thermal imaging resolution: 160 * 120 Visible light resolution: 200W Power supply: dc12-24 V Temperature range: - 20 ℃ ~ 150 ℃ Accuracy: ± 2 ℃ or 2% of the reading (take the maximum absolute value)

Space UHF PD sensor


Detection frequency band: 300 ~ 1500mhz Protection grade: IP65 Collect the discharge amplitude and phase The service life is more than 8 years

Micro weather sensor


Temperature: measuring range - 40 ~ 60 ℃ ° C Accuracy ± zero point one ° C; two Temperature: measurement range 0 ~ 100% RH Air pressure: measuring range: 10 ~ 1300 Wind speed measurement range: 0-75 M / S

Switch cabinet partial discharge sensor (UHF)


The system adopts UHF principle to conduct local discharge monitoring of high voltage switchgear to ensure the effective monitoring data, and increase system reliability. Ultra low power consumption and 485 bus communication mode are adopted. It is applicable to switch cabinet and ring network cabinet. Each cabinet is equipped with one set to realize the power / qualitative measurement of local discharge. It can be directly connected to the system host without the limitation of host channel.)

Switch cabinet partial discharge sensor (UHF + AE two in one)


The system adopts UHF + AE principle Ultra low power consumption and 485 bus communication mode are adopted, It is suitable for switch cabinet and ring main unit to realize the quantity / qualitative measurement of partial discharge

Intelligent air conditioning / dehumidification linkage device


AC / dc220v power supply is adopted Allowable deviation - 20% ~ + 20% Control output node capacity: AC / dc220v, ≥ 8A Support 2-4 independent node output capability

Welcome your message consultation

Our staff will contact you within 24 hours (weekdays), if you need other services, please call the service hotline:0519-85851518