无线温湿度传感器

无线测温湿度是将传感器安装到需要监测环境温湿度的现场,以无线方式将实时采集到的温度、湿度数据上传,集中显示,并实现超温、超湿报警。还可与电力自动化系统连接,用户在远端监视设备温湿度运行状态,系统发现设备温湿度异常,自动远程报警及时发现事故隐患。

Keyword:

Power IoT sensors Smart power distribution Internet of Things Smart cable tunnel gallery Smart power generation Internet of Things Smart Internet of Things

Free consultation telephone:

Product Details

无线温湿度传感器

 

 

产品概述

 

 

   无线温湿度传感器采用高精度温湿度探头,采用LoRa无线传输方式,无需现场布线,替换传统的有线数据采集产品。数据测量准确,传输灵敏度高,误码率低,安装简单,成本低,使用寿命长。
 

 

技术参数

 

 

  ◇ 供电电压:锂亚电池DC3.6V;  

  ◇ 功   耗:休眠状态≤30μA;

              通信状态 ≤50mA;

  ◇ 量   程:温度:-40℃~85℃;

              湿度:0~99.9%RH;            

  ◇ 灵敏度: 温度:±0.5℃(0~60℃);

              湿度:±1%RH;  

  ◇ 环境温度:-40~+80℃;

  ◇ 环境湿度:0~95%RH;    

  ◇ 传输方式:采用基于LoRa的2.4GHz频段无线通信,满足输变电设备物联网微功率无线网通信协议;

  ◇ 无线传输距离:大于50米;

  ◇ 响应时间:1min/次;

  ◇ 数据上送频率:出厂配置1次/15分钟,可根据买方要求进行灵活配置,配置上送频率范围应包括1次/分钟至1次/60分钟;

  ◇ 使用寿命:≥5年;

  ◇ 安装方式:壁挂式。

 

 

Related Products

Current monitoring sensor of arrester in switchgear


Full current measurement range: 0.050 ~ 5.000mA Full current measurement error: ± (standard reading ×1%+5μA) Record the cumulative discharge times :0 ~ 99 times Power supply: DC24V Communication interface: RS-485

Ground resistance sensor


Power supply: dc6 ~ 12V Range: 0.01 Ω- two hundred Ω  Accuracy: ± 2%rdg ± 3dgt(20℃ ± 5 ℃, below 70% RH) Communication mode: RS485 Protection grade: IP54

High frequency current sensor


Sensitivity: 5pc Detection frequency band: 50KHz ~ 100MHz Signal output: RS485 Installation position: cable connector ground wire Installation mode: clamp type, clamping

Tilt sensor


Range: ± thirty °  Voltage: 9-35v Output mode: RS485 IP67 protection level

Infrared thermal imaging camera of switch cabinet


Thermal imaging resolution: 160 * 120 Visible light resolution: 200W Power supply: dc12-24 V Temperature range: - 20 ℃ ~ 150 ℃ Accuracy: ± 2 ℃ or 2% of the reading (take the maximum absolute value)

Space UHF PD sensor


Detection frequency band: 300 ~ 1500mhz Protection grade: IP65 Collect the discharge amplitude and phase The service life is more than 8 years

Micro weather sensor


Temperature: measuring range - 40 ~ 60 ℃ ° C Accuracy ± zero point one ° C; two Temperature: measurement range 0 ~ 100% RH Air pressure: measuring range: 10 ~ 1300 Wind speed measurement range: 0-75 M / S

Switch cabinet partial discharge sensor (UHF)


The system adopts UHF principle to conduct local discharge monitoring of high voltage switchgear to ensure the effective monitoring data, and increase system reliability. Ultra low power consumption and 485 bus communication mode are adopted. It is applicable to switch cabinet and ring network cabinet. Each cabinet is equipped with one set to realize the power / qualitative measurement of local discharge. It can be directly connected to the system host without the limitation of host channel.)

Switch cabinet partial discharge sensor (UHF + AE two in one)


The system adopts UHF + AE principle Ultra low power consumption and 485 bus communication mode are adopted, It is suitable for switch cabinet and ring main unit to realize the quantity / qualitative measurement of partial discharge

Intelligent air conditioning / dehumidification linkage device


AC / dc220v power supply is adopted Allowable deviation - 20% ~ + 20% Control output node capacity: AC / dc220v, ≥ 8A Support 2-4 independent node output capability

Intelligent light control unit


Output mode: switch type, realize local and remote control of lighting Wall mounted / 2U rack mounted Using brand devices to ensure reliability Size (mm): 480mm long × 85mm wide × 340mm deep

Intelligent water pump control unit


Output mode: switch type, realize the linkage control of water pump Wall mounted / 2U rack mounted, Using brand devices to ensure reliability Size (mm): 480mm long × 85mm wide × 340mm deep

Welcome your message consultation

Our staff will contact you within 24 hours (weekdays), if you need other services, please call the service hotline:0519-85851518