搜索
Product system
Your current location:
Homepage
-
-
-
-
-
On-site detection, diagnosis and fault location system for partial discharge of high-voltage cables
Number of views:
1000

On-site detection, diagnosis and fault location system for partial discharge of high-voltage cables

It is used for on-site frequency conversion resonance voltage test of 10kV~220kV high-voltage cables, on-site partial discharge detection and fault location under oscillating waves. It can conduct AC withstand voltage and partial discharge fault location tests on high-voltage cables with a length of 0.2km-8km.
Free telephone number:0519-85851518
Retail price
0.0
Market price
0.0
Number of views:
1000
Product serial number
Quantity
-
+
Stock:
0
Product description
Parameters

Damping AC output voltage: 5kV~220kV

Damping AC voltage frequency range: 30Hz~300Hz

Test cable length: 0.2km~8km (equivalent capacitance range: 0.05μF~2μF)

Pressure method: AC resonance boost

Partial discharge detection frequency band: 30kHz~45MHz

Partial discharge test range: 1pC~100nC (1pC~5pC can be measured in the laboratory)

Fault location accuracy: ±2m

Partial discharge testing standard: in line with IEC 60270 standard

Withstand voltage test standard: in line with GB50150-2006 standard

Functional characteristics: withstand voltage test, partial discharge field detection, fault diagnosis and location; anti-interference technology such as digital filtering, dynamic threshold, wavelet analysis, time delay identification; discharge spectrum, fault location spectrum, discharge phase spectrum, number of discharges Spectrogram, discharge type recognition and other functions.

We could not find any corresponding parameters, please add them to the properties table