Partial discharge has become an important cause of insulation deterioration of power transformers, so the monitoring and evaluation of partial discharges has become an important means of monitoring the insulation status. At present, the popular methods for monitoring the partial discharge state of transformers mainly include the UHF method. The FC-9625 transformer partial discharge monitoring device is a UHF method. System composition: 1 sensor (ultra high frequency), four-channel data processing unit (partial discharge IED), station-side server, and professional analysis and diagnosis system software.

Keyword:

Power IoT sensors Smart power distribution Internet of Things Smart cable tunnel gallery Smart power generation Internet of Things Smart Internet of Things

Free consultation telephone:

Product Details

Working mode: built-in UHF sensor or external UHF sensor, continuous online monitoring

Ultra high frequency (UHF) frequency range: 300~1500MHz

Built-in UHF sensor: ≤5pC

External ultra-high frequency sensor: ≤10pC

Data processing sampling period: ≤20μs

Data format: The device has a data transmission interface. It should be connected to CMA directly or through the DL/T 860 protocol of TCP/IP to communicate with CAC. The configuration and modeling should be carried out in strict accordance with the relevant requirements of State Grid Corporation and Zhejiang Electric Power Company (see appendix for details) to realize services such as data reading and writing, reports, logs and files, and upload the device's own alarm through the data quality.

Ability to expand the number of collection stations: no less than 120 monitoring points for a single system

System design service life: ≥10 years

Related Products

Current monitoring sensor of arrester in switchgear


Full current measurement range: 0.050 ~ 5.000mA Full current measurement error: ± (standard reading ×1%+5μA) Record the cumulative discharge times :0 ~ 99 times Power supply: DC24V Communication interface: RS-485

Ground resistance sensor


Power supply: dc6 ~ 12V Range: 0.01 Ω- two hundred Ω  Accuracy: ± 2%rdg ± 3dgt(20℃ ± 5 ℃, below 70% RH) Communication mode: RS485 Protection grade: IP54

High frequency current sensor


Sensitivity: 5pc Detection frequency band: 50KHz ~ 100MHz Signal output: RS485 Installation position: cable connector ground wire Installation mode: clamp type, clamping

Tilt sensor


Range: ± thirty °  Voltage: 9-35v Output mode: RS485 IP67 protection level

Infrared thermal imaging camera of switch cabinet


Thermal imaging resolution: 160 * 120 Visible light resolution: 200W Power supply: dc12-24 V Temperature range: - 20 ℃ ~ 150 ℃ Accuracy: ± 2 ℃ or 2% of the reading (take the maximum absolute value)

Space UHF PD sensor


Detection frequency band: 300 ~ 1500mhz Protection grade: IP65 Collect the discharge amplitude and phase The service life is more than 8 years

Micro weather sensor


Temperature: measuring range - 40 ~ 60 ℃ ° C Accuracy ± zero point one ° C; two Temperature: measurement range 0 ~ 100% RH Air pressure: measuring range: 10 ~ 1300 Wind speed measurement range: 0-75 M / S

Switch cabinet partial discharge sensor (UHF)


The system adopts UHF principle to conduct local discharge monitoring of high voltage switchgear to ensure the effective monitoring data, and increase system reliability. Ultra low power consumption and 485 bus communication mode are adopted. It is applicable to switch cabinet and ring network cabinet. Each cabinet is equipped with one set to realize the power / qualitative measurement of local discharge. It can be directly connected to the system host without the limitation of host channel.)

Switch cabinet partial discharge sensor (UHF + AE two in one)


The system adopts UHF + AE principle Ultra low power consumption and 485 bus communication mode are adopted, It is suitable for switch cabinet and ring main unit to realize the quantity / qualitative measurement of partial discharge

Intelligent air conditioning / dehumidification linkage device


AC / dc220v power supply is adopted Allowable deviation - 20% ~ + 20% Control output node capacity: AC / dc220v, ≥ 8A Support 2-4 independent node output capability

Intelligent light control unit


Output mode: switch type, realize local and remote control of lighting Wall mounted / 2U rack mounted Using brand devices to ensure reliability Size (mm): 480mm long × 85mm wide × 340mm deep

Intelligent water pump control unit


Output mode: switch type, realize the linkage control of water pump Wall mounted / 2U rack mounted, Using brand devices to ensure reliability Size (mm): 480mm long × 85mm wide × 340mm deep